PARAMETER SETTINGS

6.10 Refresh Parameter Setting

The refresh parameters are designed to transfer link devices (LX, LY, LB, and LW) of CC-
Link IE Controller Network board to the driver buffers (LX, LY, LB, and LW buffers) of a
personal computer to be used in user programs.
The refresh parameter settings are set on the "Refresh parameter setting" screen of the
CC IE Control utility.
Section 8.4.9 Refresh parameter setting screen
6
- 25
6.10 Refresh Parameter Setting
POINT
(1) Set only the link devices used for the personal computer side to the link
refresh range. The link refresh time can be shortened by decreasing the link
refresh points for the personal computer side.
(2) If the network range assignment is changed, check the link refresh range as
well.
(3) When setting the refresh parameters, use the 1.08J or later version of CC IE
Control utility.
(For checking versions Appendix 6 Checking Serial Number and
Function Version)
• If the parameter file set and written on the 1.07H or earlier version of CC
IE Control utility is read by the 1.08J or later version, initial settings are
set for the refresh parameters.
• If the parameter file set and written on the 1.08J or later version of CC IE
Control utility is read by the 1.07H or earlier version, a file read error
occurs.
Version to which
parameter file is written
1.07H or earlier
1.08J or later
(4) The refresh parameter settings are not required for SB/SW since the link
device storage area is accessed directly when reading/writing SB/SW.
Version from which parameter file is read
1.07H or earlier
(No settings)
File read error
1.08J or later
Initial values
Set values