14
TROUBLESHOOTING
14.4.4 Flowchart when data link among whole system is disabled
An error occurred.
Is parameter set to the
control station?
YES
Is the control station mode
set to "ONLINE"?
YES
Is the monitoring time set for the
link parameter greater than the
link scan time?
YES
Is the "RUN" LED of the
control station ON?
YES
Are the "RUN" LEDs
from the start to the end
stations ON?
YES
1)
To the next page
14
- 18
14.4 Flowchart when Data Link Failed
14.4.4 Flowchart when data link among whole system is disabled
NO
Set a parameter.
NO
Did data link start?
NO
When the control station is a programmable
controller, correct the setting number and
reset the controller.
NO
Did data link start?
NO
Correct the setting value for the monitoring time.
NO
Did data link start?
NO
NO
2)
To the next page
YES
YES
End
YES
3)
To the next page