Fieldbus Block Information
OUNDATION
22
FSTATE_VAL5
23
FSTATE_VAL6
24
FSTATE_VAL7
25
FSTATE_VAL8
26
FSTATE_STATUS
27
UPDATE_EVT
28
BLOCK_ALM
F
OUNDATION
The preset analog value to use when failure occurs in IN_5. Ignored if
the "Fault state to value 5" in the MO_OPTS parameter is false.
The preset analog value to use when failure occurs in IN_6. Ignored if
the "Fault state to value 6" in the MO_OPTS parameter is false.
The preset analog value to use when failure occurs in IN_7. Ignored if
the "Fault state to value 7" in the MO_OPTS parameter is false.
The preset analog value to use when failure occurs in IN_8. Ignored if
the "Fault state to value 8" in the MO_OPTS parameter is false.
Shows which points are in fault state.
This alert is generated by any change to the static data.
The block alarm is used for all configuration, hardware, connection
failure or system problems in the block. The cause of the alert is
entered in the subcode field. The first alert to become active will set
the Active status in the Status parameter. As soon as the Unreported
status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active status, if the subcode has
changed.
Fieldbus Block Information
July 2017
137