Configuration and operation
March 2021
4.12
Multiple Analog Output blocks
To show input data from MAO blocks on the display, the Rosemount 2230 needs to be
configured by using F
Transducer Block.
Related information
Display Transducer block
Configure the MAO blocks
4.12.1
Configure the MAO blocks
Configure the MAO blocks
A MAO Block is used for receiving measurement data from devices such as the Rosemount
5900S Radar Level Gauge. The Rosemount 2230 is supplied with four pre-configured MAO
blocks according to
Note that the CHANNEL parameter value has to be equal to 1 (auto) in order to provide
data output from the MAO block.
An example of a setup with a Rosemount 2230 receiving data from a Rosemount 5900S
and a Rosemount 2240S is shown in
Application example
Figure 4-12
and temperature measurement data from devices such as the Rosemount 5900S Radar
Level Gauge and the Rosemount 2240S Temperature Transmitter.
74
™
Fieldbus parameters which are available in the Display
OUNDATION
Table
4-6. Each MAO block has eight inputs.
Figure
shows a Rosemount 2230 Graphical Field Display configured for receiving level
4-12.