Configuration and Operation
July 2017
8. Proceed with configuration of Multiple Analog Output (MAO) blocks by pressing the appropriate
button; Multiple Analog Output Block #.
9. The Multiple Analog Output Block window lets you map tanks and tank parameters from the Multiple
Analog Output (MAO) block inputs 1 - 8 to the tanks and tank parameters in the Rosemount 2230
transducer block. This configuration is required in order to make the field device parameters available
on the display output. See section
on MAO blocks.
Note that MAO Block 1 to MAO Block 4 refer to index number 1400 to 1700 (MAO_1400 - MAO_1700).
See section
For each tank you may not configure more than one Tank Parameter of a certain type. This means that for
each tank you may specify one Level, one Liquid Temperature, etc.
The Bar Graph Minimum and Maximum Value correspond to 0 % and 100 %, respectively. In case you
don't want any bar graph to be displayed simply leave Minimum Value=0 and Maximum Value=0.
Configure all inputs that are used for the MAO Block.
Note that tank names can be configured in the Manual Setup window, see
In case there is no tank parameter available that matches the output from a specific device in the fieldbus
network, a custom parameter can be used instead. A custom parameter can be anything from any device
in the network. Custom parameters can be configured in the Custom Parameters window as described
below.
72
"Factory configuration" on page 59
"Multiple Analog Output blocks" on page 59
for more information.
Reference Manual
00809-0100-2230, Rev CA
for more information
"Manual setup" on page
Configuration and Operation
75.