Service and Troubleshooting
July 2017
5.3.3
Foundation Fieldbus system
This section covers Rosemount Tank Gauging systems in F
Table 5-5. Troubleshooting chart for Foundation Fieldbus related problems
Symptom
No communication with
the Rosemount 2230
Configuration can not be
saved
Activity indicator shows a
warning symbol
Wrong unit appears on
the display
Cannot commission the
display to Foundation
fieldbus segment
92
Possible cause
No temporary address
available in the FOUNDATION
fieldbus segment
The device address is within a
range that is not probed by
the Link Active Scheduler
(LAS)
Missing or too many
terminations
•
Write protection switch is set
to the ON position
•
Software Write Protect is
enabled
•
Communication failure
•
Out of Service (OOS)
•
Incorrect configuration in
AMS Device Manager.
Measurement unit that was
chosen in the Display Setup
window does not match
selected unit in the Manual
Setup window
•
Missing Device Description
(DD)
Fieldbus networks.
OUNDATION
Action
There is more than four new devices on the
FOUNDATION fieldbus segment. Wait until a temporary
address is available.
Make sure that the device address is scanned by the
LAS.
Ensure that there are two terminations on the
F
fieldbus segment.
OUNDATION
•
Check write protection switch on the Rosemount 2230
•
Disable software write protect. See
page
107.
•
See "No communication with the Rosemount 2230"
•
Set the device to "Auto" mode
Ensure that the "Default" option is selected for Unit in
the Manual Setup window
Add Rosemount 2230 DD to the FF host
Reference Manual
00809-0100-2230, Rev CA
"Write protection" on
Service and Troubleshooting