Configuration and Operation
July 2017
4.12.5
Alarm priority
Alarms are grouped into five levels of priority:
Table 4-7. Alarm level priority
Priority
Number
0
1
2
3-7
8-15
68
Priority Description
The priority of an alarm condition changes to 0 after the condition
that caused the alarm is corrected.
An alarm condition with a priority of 1 is recognized by the system,
but is not reported to the operator.
An alarm condition with a priority of 2 is reported to the operator,
but does not require operator attention (such as diagnostics and
system alerts).
Alarm conditions of priority 3 to 7 are advisory alarms of increasing
priority.
Alarm conditions of priority 8 to 15 are critical alarms of increasing
priority.
Reference Manual
00809-0100-2230, Rev CA
Configuration and Operation