Out of specification alerts
An Out of Specification alert indicates that the device operates out of the specified measurement range. If
the condition is ignored, the device will eventually fail. There are five parameters associated with
FD_OFFSPEC_ALM, they are described below.
FD_OFFSPEC_MAP
The FD_OFFSPEC_MAP parameter contains a list of conditions indicating that the device or some part of
the device operates out of specification. Below is a list of the conditions with the highest priority first.
This priority is not the same as the FD_OFFSPEC_PRI parameter described below. It is hard coded within
the device and is not user configurable.
Below is a list of the conditions:
1. Invalid Model Code
2. Internal Temperature Out of Limits
3. MAO Fault State Mode Enabled
FD_OFFSPEC_MASK
The FD_OFFSPEC_MASK parameter will mask any of the failed conditions listed in FD_OFFSPEC_MAP. A
bit on means that the condition is masked out from alarming and being broadcast to the host through
the alarm parameter.
FD_OFFSPEC_PRI
This parameter designates the alarming priority of the FD_OFFSPEC_ALM, see
page
FD_OFFSPEC_ACTIVE
The FD_OFFSPEC_ACTIVE parameter displays which of the conditions is detected as active.
FD_OFFSPEC_ALM
An alarm indicating that the device operates out of the specified measurement range. If the condition is
ignored, the device will eventually fail.
Configuration and Operation
68. The default is 0 and the recommended values are 3 to 7.
Configuration and Operation
"Alarm priority" on
July 2017
65