The standard start-up procedure of a Rosemount Tank Gauging system that includes devices such as the
Rosemount 2460 System Hub, Rosemount 2410 Tank Hub, Rosemount 5900S Radar Level Gauge, and
the Rosemount 2240S Multi-input Temperature Transmitter can be summarized as follows:
1. Install the devices on the appropriate locations.
2. Assign Modbus addresses
Rosemount 5900S Radar Level Gauge, and for auxiliary tank devices (ATD) such as the Rosemount
2240S Multi-input Temperature Transmitter. The Modbus addresses will be stored in the built-in
databases of the Rosemount 2410 Tank Hub and the Rosemount 2460 System Hub.
3. Verify that the total current consumption of devices connected to the Tankbus does not exceed
250 mA
4. Wire the devices.
Connect field devices to the Tankbus.
Note! Devices must be configured in the tank database
to be able to communicate on the Tankbus.
Connect the Rosemount 2410 Tank Hub to the Rosemount 2460 System Hub.
Connect the Rosemount 2460 System Hub to the control room PC with TankMaster software. The
2460 may be connected via a Rosemount 2180 Field Bus Modem, or directly via RS 232 or RS 485.
5. Install the TankMaster software in the control room PC.
6. Configure the devices by using the TankMaster WinSetup configuration tool as described in the
Rosemount Tank Gauging System Configuration Manual (Document no. 00809-0300-5100).
F
OUNDATION
To start up Rosemount Tank Gauging devices in a F
1. Prepare the start-up by recording information that will be needed for configuration of various field
devices as described in the Rosemount Tank Gauging System Configuration manual. This may for
example include tank geometry, antenna type, number of temperature elements and other
configuration parameters.
2. Connect the field devices, such as the Rosemount 5900S Radar Level Gauge and the Rosemount
2240S Multi-input Temperature Transmitter, to the F
3. Configure the field devices by using AMS Device Manager (or any other F
supporting DD4).
See the Reference Manual for the respective field device and the Rosemount Tank Gauging System
Configuration manual (Document No. 00809-0300-5100) for more information on how to configure
various Rosemount Tank Gauging devices. See section
available documentation.
1.
See the Rosemount Tank Gauging System Configuration Manual (Document no. 00809-0300-5100) for more information
2.
See the Rosemount 2410 Tank Hub Reference Manual (Document No. 00809-0100-2410) for more information
16
(1)
for the Rosemount 2410 Tank Hub, for level gauges such as the
(2)
. In an Emerson Wireless system the maximum current is 200 mA.
fieldbus
(1)(2)
of the Rosemount 2410 Tank Hub in order
fieldbus system:
OUNDATION
fieldbus network.
OUNDATION
"Technical documentation" on page 4
Reference Manual
00809-0100-2230, Rev CA
fieldbus host
OUNDATION
for a list of