Product Certifications
July 2017
B.4 North America
I5
USA Intrinsic Safety
Certificate: FM17US0035X
Standards: FM Class 3600 – 2011,
FM Class 3610 – 2010,
FM Class 3810 – 2005,
ANSI/NEMA 250 – 2008,
ANSI/IEC 60529 – 2004,
ANSI/ISA 61010-1:2004
ANSI/ISA 60079-0 – 2013,
ANSI/ISA 60079-11 – 2013,
Markings: IS/I,II,III/1/ABCDEFG/T4 Ta = -50°C to +70°C
Control Dwg D9240040-949
I/0/AEx ia IIC Ga T4 Ta = -50°C to +70°C Control
Control Dwg D9240040-949
Type 4X; IP66, IP67
Ui
Entity parameters
30 V
FISCO parameters
17.5V
Specific Conditions for Safe Use (X):
1. The non-metallic parts incorporated in the enclosure of this
equipment may generate an ignition-capable level of
electrostatic charge. Therefore particularly when it is used for
applications that specifically require Division 1 and Group II,
Zone 0 located equipment, the equipment shall not be
installed in a location where the external conditions are
conducive to the build-up of electrostatic charge on such
surfaces. Additionally, the equipment shall only be cleaned
with a damp cloth.
2. The enclosure contains aluminum and is considered to
present a potential risk of ignition by impact or friction. Care
must be taken during installation and use to prevent impact
or friction.
3. The Rosemount 2230 Graphical Field Display will not pass the
500Vrms dielectric strength test and this must be taken into
account during installation.
4. To maintain ingress protection ratings IP66 and IP67, PTFE
tape or pipe dope is required for cable entries and blanking
plugs.
118
Ii
Pi
Ci
300 mA
1.3 W
2.1 nF
380 mA
5.32 W N/A
I6
Canada Intrinsic Safety
Certificate: FM17CA0019X
Standards: CAN/CSA C22.2 No.157-1992 (R2012)
Markings: IS/I,II,III/1/ABCDEFG/T4 Ta = -50°C to +70°C
Entity parameters
Li
FISCO parameters
1.1 μH
Specific Conditions for Safe Use (X):
N/A
1. The non-metallic parts incorporated in the enclosure of this
equipment may generate an ignition-capable level of
electrostatic charge. Therefore particularly when it is used for
applications that specifically require Division 1 and Group II,
Zone 0 located equipment, the equipment shall not be
installed in a location where the external conditions are
conducive to the build-up of electrostatic charge on such
surfaces. Additionally, the equipment shall only be cleaned
with a damp cloth.
2. The enclosure contains aluminum and is considered to
present a potential risk of ignition by impact or friction. Care
must be taken during installation and use to prevent impact
or friction.
3. The Rosemount 2230 Graphical Field Display will not pass the
500Vrms dielectric strength test and this must be taken into
account during installation.
4. To maintain ingress protection ratings IP66 and IP67, PTFE
tape or pipe dope is required for cable entries and blanking
plugs.
Reference Manual
00809-0100-2230, Rev CA
CAN/CSA C22.2 No. 1010.1:2004
CAN/CSA C22.2 No. 25-1966 (R2014)
CAN/CSA C22.2 No. 94-M91:1991 (R2011)
CAN/CSA-C22.2 No. 60529-2005 (R2015)
CAN/CSA C22.2 No. E60079-0:2011
CAN/CSA C22.2 No. E60079-11:2011
Control Dwg D9240040-949
I/0/Ex ia IIC Ga T4 Ta = -50°C to +70°C
Control Dwg D9240040-949.
Type 4X; IP66, IP67
Ui
Ii
Pi
30 V
300 mA 1.3 W
17.5V
380 mA 5.32 W N/A
Ci
Li
2.1 nF
1.1 μH
N/A
Product Certifications