Reference Manual
00809-0100-2230, Rev CA
Figure 4-12. Example of MAO block configuration using AMS Device Manager
Configuration and Operation
Configuration and Operation
In control strategy software, such as Control
Studio, function blocks are connected to
various tank process variables. In AMS Device
Manager the Guided Setup provides easy
access for configuration of function blocks that
are available for the Rosemount 2230.
The Control Studio diagram in
shows which tank variables that are connected
to the Multiple Analog Output blocks in this
example. MAO Block 1 and MAO Block 2 are
configured by using AMS Device Manager as
shown in this example.
MAO Block 1 is configured for Level, Liquid
Temperature, and Free Water Level.
MAO Block 2 is configured for Temperature
inputs 1 to 6.
See
"Configuration using AMS Device
Manager" on page 70
for more information on
how to use the AMS Device Manager.