F
Fieldbus Block Information
OUNDATION
July 2017
Index
Number
55
FD_FAIL_ALM
56
FD_OFFSPEC_ALM
57
FD_MAINT_ALM
58
FD_CHECK_ALM
59
FD_FAIL_PRI
60
FD_OFFSPEC_PRI
61
FD_MAINT_PRI
62
FD_CHECK_PRI
63
FD_SIMULATE
64
FD_RECOMMEN_ACT
65
FD_EXTENDED_ACTIVE
66
FD_EXTENDED_MAP
67
COMPATIBILITY_REV
68
HARDWARE_REVISION
69
SOFTWARE_REV
70
PD_TAG
71
DEV_STRING
72
DEV_OPTIONS
73
OUTPUT_BOARD_SN
74
FINAL_ASSY_NUM
75
DOWNLOAD_MODE
76
HEALTH_INDEX
77
FAILED_PRI
78
RECOMMENDED_ACTION
126
Parameter
Description
This parameter is used primarily to broadcast a change in the associated active
conditions, which are not masked, for this alarm category to a Host System.
This parameter allows the user to specify the priority of this alarm category.
This parameter allows the conditions to be manually supplied when simulation is
enabled. When simulation is disabled both the diagnostic simulate value and the
diagnostic value tracks the actual conditions. The simulate jumper is required for
simulation to be enabled and while simulation is enabled the recommended action
will show that simulation is active.
Elements: see
This parameter is a device enumerated summarization of the most severe
condition or conditions detected. The DD help should describe by enumerated
action, what should be done to alleviate the condition or conditions. 0 is defined as
Not Initialized, 1 is defined as No Action Required, all others defined by
manufacturer.
An optional parameter or parameters to allow the user finer detail on conditions
causing an active condition in the FD_*_ACTIVE parameters.
An optional parameter or parameters to allow the user finer control on enabling
conditions contributing to the conditions in FD_*_ACTIVE parameters.
This parameter is used when replacing field devices. The correct value of this
parameter is the DEV_REV value of the replaced device.
Hardware revision.
Software revision of source code with resource block.
PD tag description of device.
This is used to load new licensing into the device. The value can be written but will
always read back with a value of 0.
Indicates which miscellaneous device licensing options are enabled.
Output board serial number. For the Rosemount 2230 Display this is the same as
Main Label Device ID which can be found on the main label that is attached to the
housing.
Final assembly number given by manufacturer.
Gives access to the boot block code for over-the-wire downloads.
0 = Uninitialized
1 = Run mode
2 = Download mode
Parameter representing the overall health of the device, 100 being perfect and 1
being non-functioning. The value is based on the active PWA alarms.
Designates the alarming priority of the FAILED_ALM and also used as switch b/w FD
and legacy PWA. If value is greater than or equal to 1 then PWA alerts will be active
in device else device will have FD alerts.
Enumerated list of recommended actions displayed with a device alert.
Table C-2 on page
127.
Reference Manual