Service and Troubleshooting
July 2017
Software write protection in AMS Device Manager
A Rosemount 2230 display that is used in F
in order to prevent changes of the configuration database and fieldbus parameters.
To enable software write protection:
1. Open the AMS Device Manager software.
2. Select the Configure>Manual Setup option.
3. Select the Device tab.
4. Enable write protection by clicking the Write Protect Device button. When the Rosemount 2230 is
software write protected, the push buttons on the front of the housing can no longer be used to
change device configuration. All holding registers and Fieldbus parameters will be protected. Write
protection can be disabled at anytime by clicking the Write Protect Device button again.
Manual Setup
Configure
108
fieldbus systems can be software write protected
OUNDATION
Reference Manual
00809-0100-2230, Rev CA
Write Protect
Device
Service and Troubleshooting