Multiple analog output block
The Multiple Analog Output Block (MAO_1400 to MAO_1700) accepts output values from field devices
and assigns them to specified I/O channels in order to make them available for the display.
Table C-7. Multiple Analog Output Block
Index
Number
136
Parameter
1
ST_REV
2
TAG_DESC
3
STRATEGY
4
ALERT_KEY
5
MODE_BLK
6
BLOCK_ERR
7
CHANNEL
8
IN_1
9
IN_2
10
IN_3
11
IN_4
12
IN_5
13
IN_6
14
IN_7
15
IN_8
16
MO_OPTS
17
FSTATE_TIME
18
FSTATE_VAL1
19
FSTATE_VAL2
20
FSTATE_VAL3
21
FSTATE_VAL4
Description
The revision level of the static data associated with the function block.
The revision value increments each time a static parameter value in the
block is changed.
The user description of the intended application of the block.
The strategy field can be used to identify grouping of blocks. This data
is not checked or processed by the block.
The identification number of the plant unit. This information may be
used in the host for sorting alarms, etc.
The actual, target, permitted, and normal modes of the block.
Target: The mode to "go to"
Actual: The mode the "block is currently in"
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
This parameter reflects the error status associated with the hardware
or software components associated with a block. It is a bit string, so
that multiple errors may be shown.
Defines the output that drives the field device.
Numbered input parameter for multiple output function blocks
Numbered input parameter for multiple output function blocks
Numbered input parameter for multiple output function blocks
Numbered input parameter for multiple output function blocks
Numbered input parameter for multiple output function blocks
Numbered input parameter for multiple output function blocks
Numbered input parameter for multiple output function blocks
Numbered input parameter for multiple output function blocks
Options that the user may select to alter multiple output block
processing. In case a Fault State option is set, the 2230 will send a Field
Diagnostic alert.
The preset analog value to use when failure occurs in IN_1. Ignored if
the "Fault state to value 1" in the MO_OPTS parameter is false.
The preset analog value to use when failure occurs in IN_2. Ignored if
the "Fault state to value 2" in the MO_OPTS parameter is false.
The preset analog value to use when failure occurs in IN_3. Ignored if
the "Fault state to value 3" in the MO_OPTS parameter is false.
The preset analog value to use when failure occurs in IN_4. Ignored if
the "Fault state to value 4" in the MO_OPTS parameter is false.