Symptom (continued)
No communication with
the Rosemount 2230
Graphical Field Display
Activity indicator shows a
warning symbol
Service and Troubleshooting
Possible cause
Incorrect configuration of tank
database in Rosemount 2410
Tank Hub
Connection to Rosemount 2410
Tank Hub
Configuration of communication
protocol
Legacy system:
Connection to 2160 Field
Communication Unit (FCU)
Communication failure
Service and Troubleshooting
Action
Check the Rosemount 2410's tank database; ensure that
the Rosemount 2230 device is available and mapped to the
right tank
Rosemount 2410 tank database; check that the ATD
Modbus address is equal to the 2410 Temp Modbus address
in the Rosemount 2460 System Hub's tank database/2160
Field Communication Unit's slave database
See the Rosemount Tank Gauging System Configuration
Manual (Document no. 00809-0300-5100) for more
information on how to configure the Rosemount 2410 's
tank database
Check wiring to the Rosemount 2410 Tank Hub
Check the Rosemount 2410 Tank Hub; check the Error LED
or the integral display for information
In TankMaster WinSetup:
open the Protocols folder and check that the protocol
channel is enabled
check the protocol channel configuration (right-click the
protocol channel MbMaster icon, choose the Properties
option, and check port, parameters, modem)
Check that the right field bus port on the 2160 FCU is
connected to the Primary bus on the Rosemount 2410
Tank Hub
Check communication port LED:s inside the Field
Communication Unit 2160 (FCU)
Check that the Rosemount 2230 is configured in the
Rosemount 2410 tank database. See the Rosemount
Tank Gauging System Configuration Manual (Document
no. 00809-0300-5100) for more information on how to
configure the tank database.