F
Fieldbus Block Information
OUNDATION
July 2017
C.2

Register transducer block

The Register Transducer Block (TB 1200) allows access to Database registers and Input registers of the
Rosemount 2230 Graphical Field Display. This makes it possible to read a selected set of registers directly
by accessing the memory location.
The Register Transducer Block is only available with advanced service.
Since the Register Transducer Block allows access to most registers in the 2230, which includes the
registers set by the Methods and Configuration screens in the Level Transducer Block it should be
handled with care and ONLY to be changed by trained and certified service personnel, or as guided by
Emerson Automation Solutions/Rosemount Tank Gauging support personnel.
Table C-3. Register Transducer Block parameters
Index
Number
128
Parameter
1
ST_REV
2
TAG_DESC
3
STRATEGY
4
ALERT_KEY
5
MODE_BLK
6
BLOCK_ERR
7
UPDATE_EVT
8
BLOCK_ALM
9
TRANSDUCER_DIRECTORY
10
TRANSDUCER_TYPE
11
TRANSDUCER_TYPE_VER
12
XD_ERROR
13
COLLECTION_DIRECTORY
14
RB_PARAMETER
Description
The revision level of the static data associated with the function
block. The revision value increments each time a static
parameter value in the block is changed.
The user description of the intended application of the block.
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
The actual, target, permitted, and normal modes of the block.
Target: The mode to "go to"
Actual: The mode the "block is currently in"
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
This parameter reflects the error status associated with the
hardware or software components associated with a block. It is
a bit string, so that multiple errors may be shown.
This alert is generated by any change to the static data
The 2230 transducer block does not support update of
BLOCK_ALM information, and it does not publish BLOCK_ALM
on segment/FF bus.
Directory that specifies the number and starting indices of the
transducers in the transducer block.
Identifies the transducer.
A transducer block alarm sub code.
A directory that specifies the number, starting indices, and DD
Item ID's of the data collections in each transducer within a
transducer block.
Reference Manual