5-1-3

Setting the output magnification

(1) Meter output (Data No. 0)
With meter output, the output channel is fixed, and the output voltage range is 0 to 10V in the
positive range. Set the magnification with the following parameters.
No.
Abbr.
Parameter name
SP249
SMO
Speedometer speed
SP250
LMO
Load meter voltage
(2) Internal data output (Data No. 1 to 13, 125 to 127)
Normally, the standard setting value is set for the output magnification (SP255, SP256). When
"0" is set, the magnification will be the same as "256".
SV063
DATA ×
256
(Example) To output current FB at a 30-minute stall rating 20%/V unit (SP253=3, SP255=8)
8
819.2 ×
256
No.
Abbr.
Parameter name
DA output channel 1
SP255
DA1MPY
magnification
DA output channel 2
SP256
DA2MPY
magnification
(3) Control signal output (Data No. 80 to 87)
A hexadecimal display is converted into a decimal and output. The method of calculating the
magnification is the same as (2). The status cannot be output for each bit, so output the status for
all 16 bits.
(Example) Orientation indexing control
With orientation indexing control, the following operations of the "Control output 4" can be
observed as shown on the right:
bit4: Orientation completed
bit7: Indexing positioning completed
Note that the weight of the D/A output differs for each bit.
Motor speed
Control output 4
5. Spindle Adjustment
Set the motor rotation speed when the speedometer 10V
is output.
When set to "0", this parameter becomes the same as
SP017 (TSP).
Set the voltage when the load meter 120% is output.
When set to "0", this becomes 10V.
10 [V]
×
+ 5 [V] (offset) = Output voltage [V]
256 (8 bit)
10
×
+ 5 = 6 [V]
256
Set the output magnification with a 1/256 unit.
When "0" is set, the magnification will be the same as
"256".
10[V]
5
5[V]
0
Orientation indexing control sequence output
Details
Details
Orientation start
Orientation speed
Orientation
Indexing
complete
complete
Orientation time
Indexing time
5 - 3
Setting range Standard
0 to 32767
(r/min)
0 to 10
(V)
Setting range Standard
-32768 to
32767
(1/256-fold)
Time
0
0
0
0