Appendix 3-5-3 Servomotor power cable

Control panel
Earth with P or U clip
To drive unit
Using shield cable
(1) Use four wires (3-phase + earthing) for the power cable that are completely shielded and free from
breaks.
(2) Earth the shield on both the control panel side and motor chassis side.
(3) Earth the shield with a metal P clip or U clip.
(A cable clamp fitting can be used depending on the wire size.)
(4) Directly earth the shield. Do not solder the braided shield onto a wire and earth the end of the wire.
(5) When not using a shield cable for the power cable, use a conventional cabtyre cable. Use a metal
conduit outside the cable.
(6) Earth the power cable on the control panel side at the contact surface of the conduit connector and
control panel. (Mask the side wall of the control panel with paint.)
(7) Follow the treatment shown in the example for the conduit connector to earth the power cable on
the motor side. (Example: Use a clamp fitting, etc.)

Appendix 3-5-4 Servo/spindle motor feedback cable

Control panel
To drive unit
Appendix 3. EMC Installation Guidelines
Cannon connector
Servomotor
Shield cable
Clamp fitting
Conduit
Conduit connector
Batch shield pair cable
Control panel
To drive unit
To earthing
Cannon connector
Use a pair shield cable for the
servomotor and spindle motor
feedback cables, and ground them in
the control panel.
Cannon connector
Directly mounting a ferrite core onto
the unit connector is also effective in
suppressing noise.
A3 - 6
Earth with paint mask
Conduit connector
Cannon
connector
Servomotor
Conduit
Cabtyre cable
Using conduit
Solder