Various Functions To Control The Analog Output; Function To Specify Hold Or Clear Of The Analog Output When The Plc Cpu Is In The Stop Status; Function To Specify Executing Or Not Executing The D/A Conversion Processing (Analog Output Enable Signal); Function To Specify Enabling Or Prohibiting Of The Analog Value External Output (Analog Output Enable/Prohibit Setting) - Mitsubishi AJ65BT-64DAV User Manual

Digital-analog converter, a melsec programmable controller
Table of Contents

Advertisement

3. SPECIFICATIONS
3.4

Various Functions to Control the Analog Output

Various functions to control the analog output of the AJ65BT-64DAV/DAI are explained.
3.4.1
Using this function, the HLD/CLR terminal on the module front panel can be used to set whether to
retain or clear (i.e. to output the offset) the analog output value immediately before the PLC CPU
enters the STOP status or before the AJ65BT-64DAV/DAI stops the D/A conversion due to an error.
All channels are set simultaneously. (Including a time when link communications are shut off)
3.4.2
Using this function, whether to output the D/A conversion value or the offset value can be selected for
each channel by turning on or off the analog output enable signal from the PLC program.
However, the D/A conversion time (conversion speed) is constant regardless of the setting of the
analog output enable signal.
3.4.3
Using this function, whether to enable or prohibit the external output of the analog signal can be
specified for each channel by writing "0" or "1" to the remote register's address from the PLC program.
3.4.4
When a fine I/O conversion characteristic is required, the I/O conversion characteristics can be
modified arbitrarily by setting the offset and gain of each channel without a volume control, after
entering the test mode by short-circuiting the test mode terminal. When it is not necessary, turning on
the RYn4, which is the I/O signal to the master station, selects the factory-configured offset and gain
values.
Factory-configured values:
AJ65BT-64DAV........ Offset value 0V, Gain value 10V
AJ65BT-64DAI ......... Offset value 4mA, Gain value 20mA
3.4.5
By combining the functions explained above, the analog output when the PLC CPU is in the RUN
status and when a module error occurs can be set as desired, as shown in Table 3.3.
Select each function depending on the analog output status of your choice.
Function to specify hold or clear of the analog output when the PLC CPU is
in the STOP status (HOLD/CLEAR setting)
Function to specify executing or not executing the D/A conversion
processing (Analog output enable signal)
Function to specify enabling or prohibiting of the analog value external
output (Analog output enable/prohibit setting)

Offset/gain setting

Combinations of various functions

ON: D/A conversion value
1: 0V/0mA
3-8
MELSEC-A
OFF: Offset value
0: D/A conversion value or offset value