Setting Annunciators, Resetting Annunciators - Mitsubishi Electric MELSEC-Q/L Programming Manual

Hide thumbs Also See for MELSEC-Q/L:
Table of Contents

Advertisement

Setting annunciators, resetting annunciators

SET F, RST F
High
Basic
Process
performance
SET
RST
SET (D) : Number of the annunciator to be set (F number) (bits)
RST (D) : Number of the annunciator to be reset (F number) (bits)
Setting
Internal device
data
Bit
 (Only F)
(D)
For details on the annunciator, refer to the User's Manual (Function Explanation, Program Fundamentals) for
the CPU module used.
Processing details
■SET
• The annunciator designated by (D) is turned ON when the execution command is turned ON.
• The following responses occur when an annunciator (F) is turned ON.
• The "USER" LED goes ON.
• The annunciator numbers which are ON (F numbers) are stored in special registers (SD64 to SD79).
• The value of SD63 is incremented by 1.
*1 When using the Basic model QCPU, the "ERR."LED goes ON.
• If the value of SD63 is 16 (which happens when 16 annunciators are already ON), even if a new annunciator is turned ON,
its number will not be stored at SD64 to SD79.
• The number of basic steps for the SET F instruction is 2.
5 SEQUENCE INSTRUCTIONS
162
5.3 Output Instructions
Redundant Universal
LCPU
Command
Command
R, ZR
Word
*1
J\
U\G
Bit
Word
D
SET
D
RST
Zn
Constant
Others

Advertisement