Operation error
• In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
Error
Error details
code
4110
The value specified at (S) is 0 at execution of the SP.CONTSW instruction.
4120
The manual switching enable flag (SM1592) is OFF (disabled) at the
execution of the SP.CONTSW instruction.
4121
The SP.CONTSW instruction was executed by the standby system CPU
module in the separate mode.
The SP.CONTSW instruction was executed in the debug mode.
• If system switching was unsuccessful, the error flag (SM0) is turned ON and an error code is stored into SD0.
Error
Error details
code
6220
The tracking cable is disconnected or faulty.
Hardware fault, power-off, reset or watchdog timer error occurred in the
standby system.
Watchdog timer error occurred in the control system.
Preparations are being made for tracking transfer.
Communication time-out occurred.
A stop error, excluding watchdog timer error, occurred in the standby system.
The operating status differs between the control system and standby system.
Memory copy is being executed from the control system to the standby
system.
Writing during RUN
Network fault was detected by the standby system.
Program example
• The following program executes system switching on the rising edge of the system switching command (M100). If the
system switching command (M100) remains ON, the SP.CONTSW instruction is also executed by the new control system
CPU module after system switching. Therefore, M101 is added to the execution conditions as a consecutive switching
prevention flag.
[Ladder Mode]
11 REDUNDANT SYSTEM INSTRUCTIONS (FOR REDUNDANT CPU)
882
11.1 System Switching
Q00J/
QnH
Q00/
Q01
Q00J/
QnH
Q00/
Q01
[List Mode]
Step
Instruction
QnPH
QnPRH
QnU
QnPH
QnPRH
QnU
Device
LCPU
LCPU

Advertisement

Table of Contents
loading

Table of Contents