Pulse conversion of edge relay operation results

EGP, EGF
High
Basic
Process
performance
(D): Edge relay number where operation results are stored (bits)
Setting
Internal device
data
Bit
(D)
Processing details
■EGP
• Operation results up to the EGP instruction are stored in memory by the edge relay (V).
• Goes ON (continuity status) at the rising edge (OFF to ON) of the operation result up to the EGP instruction. If the operation
result up to the EGP instruction is other than a rising edge (i.e., from ON to ON, ON to OFF, or OFF to OFF), it goes OFF
(non-continuity status).
• The EGP instruction is used for subroutine programs, and for conducting pulse operations for programs designated by
indexing between the FOR and NEXT instructions.
• The EGP instruction can be used like an AND instruction.
■EGF
• Operation results up to the EGF instruction are stored in memory by the edge relay (V).
• Goes ON at the falling edge (from ON to OFF) of the operation result up to the EGF instruction. If the operation result up to
the EGF instruction is other than a falling edge (i.e., from OFF to ON, ON to ON, or OFF to OFF), it goes OFF (non-
continuity status).
• The EGF instruction is used for subroutine programs, and for conducting pulse operations for programs designated by
indexing between the FOR and NEXT instructions.
• The EGF instruction can be used like an AND instruction.
Operation error
• There is no operation error in the EGP or EGF instruction.
5 SEQUENCE INSTRUCTIONS
146
5.2 Association Instructions
Redundant Universal
LCPU
Command
EGP
Command
EGF
R, ZR
Word
D
D
J\
U\G
Bit
Word
Zn
Constant
Others
V