Floating-point data transfer (single precision)

EMOV(P)
Ver.
High
Basic
Process
Redundant Universal
performance
• Basic model QCPU: The serial number (first five digits) is "04122" or later.
EMOV
EMOVP
(S): Data to be transferred or number of the device to which the data to be transferred is stored (real number)
(D): The number of the device to which the transferred data will be stored (real number)
Setting
Internal device
data
Bit
Word
(S)
(D)
*1 Applicable for the Universal model QCPU, LCPU.
Processing details
• Transfers 32-bit floating decimal point type real number data being stored at the device designated by (S) to a device
designated by (D).
S
S
+1
Transfer
4.23542
32-bit floating-point
real number
• When an input value is set using a programming tool, a rounding error may occur. For precautions, refer to Page 89
Precautions.
Operation error
• There is no operation error in the EMOV(P) instruction.
LCPU
Command
Command
R, ZR
J\
Bit
D
D
+1
4.23542
32-bit floating-point
real number
EMOV
S
EMOVP
S
U\G
Zn
Word
*1
*1
D
D
Constant
Others
E
6 BASIC INSTRUCTIONS
6.4 Data Transfer Instructions
6
299