Program example
• The following program fetches, when X0 is turned ON, the 16 points3 matrix starting from X10, and stores the matrix into
the area starting from M0.
[Ladder Mode]
[Operation]
X010
X011
X012
X013 X014 X015 X016 X017 X018 X019 X01A X01B X01C X01D X01E X01F
X010
X011
X012
X013 X014 X015 X016 X017 X018 X019 X01A X01B X01C X01D X01E X01F
X010
X011
X012
X013 X014 X015 X016 X017 X018 X019 X01A X01B X01C X01D X01E X01F
Precautions
• Note that the MTR instruction directly operates on actual input and output. The output (D1) that had been turned ON by the
MTR instruction does not turn OFF when the MTR command turns OFF. Turn OFF the specified output (D1) in the
sequence program.
• The MTR instruction execution interval must be longer than the total of response time of input and output modules. If the
set interval is shorter than the value indicated above, an input cannot be read correctly. If the scan time in a sequence
program is short, select the constant scan and set the scan time longer than the total of response time.