Mitsubishi Electric MELSEC-Q/L Programming Manual page 95

Hide thumbs Also See for MELSEC-Q/L:
Table of Contents

Advertisement

■Device that indexing can be used
With the exception of the restrictions noted below, indexing can be used with devices used with contacts, coils, basic
instructions, and application instructions.
• Devices to which indexing cannot be used
Device
E
$
.
FX, FY, FD
P
I
Z
S
TR
BL
*1 SFC transfer devices and SFC block devices are devices for SFC use.
Refer to the manual below for how to use these devices.
 MELSEC-Q/L/QnA Programming Manual (SFC)
*2 For the High-speed Universal model QCPU, the SFC block device (BL) and step relay (S) can be modified using indices within the
following range.
• For the SFC block device (BL), the range is BL0 to BL319.
• For the step relay (S), the range is specified in the device settings using parameters.
Note that if a step relay (S) in the SFC block is specified, index modification can be specified within the range of S0 to S511.
• Devices with limits for use with index registers
Device
Description
T, ST
• Only Z0 and Z1 can be used for timer contacts and coils.
C
• Only Z0 and Z1 can be used for counter contacts and coils.
*3 Universal model high speed type QCPU is excluded.
For timer and counter present values, there are no limits on index register numbers used.
X0
SM400
X1
SM400
*3
K100
T0
BCD
T0Z4
K4Y30
K10
C100
BCD
C100Z6
K2Y40
Description
Floating decimal point data
Character string data
Word device bit designation
Function devices
Pointers used as labels
Interrupt pointers used as labels
Index register
*2
Step relay
*1
SFC transfer devices
*1*2
SFC block device
Application example
T0Z0
C0Z1
Value set for timer
Present value of timer
Value set for counter
Present value of counter
3 CONFIGURATION OF INSTRUCTIONS
K100
T1Z1
K100
C1Z0
3.3 Indexing
3
93