■DFRO
• Reads the data of (n32) words from the CPU shared memory address designated by n2 of the CPU module designated
by n1, and stores that data into the area starting from the device designated by (D).
Device memory
D
• When 0 is specified in n3 as the number of data to be read, no processing is performed.
• The number of data to be read changes depending on the target CPU module.
CPU module
Basic model QCPU
Universal model QCPU
• An instruction which has been executed will result in non-processing if it fails to access the target module because the
module is faulty or busy in processing.
Read of data from the CPU shared memory can also be performed using the intelligent function module
devices.
For intelligent function module device, refer to the User's Manual (Function Explanation, Program
Fundamentals) for the CPU module used.
Operation error
• In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and an error code is stored into SD0.
Error
Error details
code
2110
No CPU module is installed at the position specified for the head I/O number
of the CPU module.
4101
The head of the CPU shared memory address (n2) which performs reading
is outside the CPU shared memory range.
The address of the CPU shared memory (n2) which performs reading + the
number of read points (n3) is outside the CPU shared memory range.
The read data storage device number (D) plus the number of read points
(n3) is outside the specified device range.
When the head of the CPU shared memory address (n2) which performs
reading is an invalid value. (4097 to 9999)
Program example
• The following program stores 10 points of data from address C0H of the CPU shared memory of CPU No. 2 into the area
starting from D0 when X0 is turned ON.
[Ladder Mode]
• The following program stores 20 points of data from address 10000 of the CPU shared memory of CPU No. 4 into the area
starting from D0 when X0 is turned ON.
[Ladder Mode]
9 MULTIPLE CPU DEDICATED INSTRUCTIONS
858
9.2 Reading from the CPU Shared Memory of Another CPU
CPU shared memory of the
designated CPU (n1)
n2
Reads the data
of (n3 2)
words
n3
Number of read points
1 to 256
1 to 7168
Q00J/
QnH
Q00/
Q01
[List Mode]
Step
Instruction
[List Mode]
Step
Instruction
QnPH
QnPRH
QnU
Device
Device
LCPU