ABB RED615 Technical Manual page 885

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
615 series
Technical Manual
Table 710:
Environmental tests
Description
Dry heat test
Dry cold test
Damp heat test
Change of temperature test
Storage test
1) For IEDs with an LC communication interface the maximum operating temperature is +70
2) For RED615 +70
o
C, 16 h
Table 711:
Product safety
Description
LV directive
Standard
Table 712:
EMC compliance
Description
EMC directive
Standard
IED and functionality tests
Type test value
96 h at +55ºC
16 h at +85ºC
1)2)
96 h at -25ºC
16 h at -40ºC
6 cycles (12 h + 12 h) at
+25°C...+55°C, humidity
>93%
5 cycles (3 h + 3 h)
at -25°C...+55°C
96 h at -40ºC
96 h at +85ºC
Reference
2006/95/EC
EN 60255-27 (2005)
EN 60255-1 (2009)
Reference
2004/108/EC
EN 50263 (2000)
EN 60255-26 (2007)
Section 15
Reference
IEC 60068-2-2
IEC 60068-2-1
IEC 60068-2-30
IEC60068-2-14
IEC 60068-2-1
IEC 60068-2-2
o
C
879

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents