Section 4
Protection functions
358
I
I
L
1
L
3
I
=
L mLV
1
3
GUID-AFF5341B-32F8-457B-86A2-6A05B950FF29 V1 EN
I
I
L
2
L
1
=
I
L mLV
2
3
GUID-FE2E9619-077C-4E9A-99A7-C6DD02A34590 V1 EN
I
I
L
3
L
2
=
I
L mLV
3
3
GUID-99D25F61-7857-4410-86E4-E1DC1B3D5F40 V1 EN
The "Y" side currents stay untouched, while the "d" side currents are compensated
to match the currents actually flowing in the windings.
In this example there is no neutral current on either side of the transformer
(assuming there are no earthing transformers installed). In the previous example,
the matching is done differently to have the winding 1 neutral current compensated
at the same time.
Table 330:
LNPLDF vector group matching
Vector group of the
Winding 1 type
transformer
Yy0
YNy0
YNyn0
Yyn0
Yy2
YNy2
YNyn2
Yyn2
Yy4
YNy4
YNyn4
Yyn4
Yy6
YNy6
YNyn6
Yyn6
Yy8
YNy8
YNyn8
Yyn8
Table continues on next page
Winding 2 type
Y
y
YN
y
YN
yn
Y
yn
Y
y
YN
y
YN
yn
Y
yn
Y
y
YN
y
YN
yn
Y
yn
Y
y
YN
y
YN
yn
Y
yn
Y
y
YN
y
YN
yn
Y
yn
1YHT530004D05 D
(Equation 36)
(Equation 37)
(Equation 38)
Phase shift
Zero sequence
current elimination
0
Not needed
0
HV side
0
HV & LV side
0
LV side
2
Not needed
2
(Automatic)
2
(Automatic)
2
(Automatic)
4
Not needed
4
(Automatic)
4
(Automatic)
4
(Automatic)
6
Not needed
6
HV side
6
HV & LV side
6
LV side
8
Not needed
8
(Automatic)
8
(Automatic)
8
(Automatic)
Technical Manual
615 series