ABB RED615 Technical Manual page 880

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Section 14
Technical data
874
Table 696:
Signal outputs and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load
Table 697:
Double-pole power output relays with TCS function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC (two
contacts connected in series)
Minimum contact load
Trip-circuit supervision (TCS):
Control voltage range
Current drain through the supervision circuit
Minimum voltage over the TCS contact
Table 698:
Single-pole power output relays
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry for 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load
Value
250 V AC/DC
5 A
10 A
15 A
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
Value
250 V AC/DC
8 A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
Value
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
1YHT530004D05 D
615 series
Technical Manual