ABB RED615 Product Manual
ABB RED615 Product Manual

ABB RED615 Product Manual

Line differential protection and control
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

®
Relion
615 series
Line Differential Protection and Control
RED615
Product Guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RED615

  • Page 1 ® Relion 615 series Line Differential Protection and Control RED615 Product Guide...
  • Page 2: Table Of Contents

    17. Protection communication and supervision....18 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.
  • Page 3: Description

    2. Standard configurations zone. RED615 relays communicate between substations over a RED615 is available in five alternative standard configurations. fiber optic link or a galvanic pilot wire connection. RED615 is a The standard signal configuration can be altered by means of ®...
  • Page 4 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 RED615 LINE DIFFERENTIAL PROTECTION AND CONTROL RELAY STANDARD With in-zone power transformer support CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Binary Signal Transfer function (BST) 2× - Disturbance and fault recorder...
  • Page 5 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 RED615 LINE DIFFERENTIAL PROTECTION AND CONTROL RELAY STANDARD With in-zone power transformer support CONFIGURATION PROTECTION LOCAL HMI ALSO AVAILABLE - Binary Signal Transfer function (BST) 2× - Disturbance and fault recorder...
  • Page 6 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 RED615 LINE DIFFERENTIAL PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION With in-zone power transformer support PROTECTION LOCAL HMI ALSO AVAILABLE - Binary Signal Transfer function (BST) 2× - Disturbance and fault recorder...
  • Page 7 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 RED615 LINE DIFFERENTIAL PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION With in-zone power transformer support PROTECTION LOCAL HMI ALSO AVAILABLE - Binary Signal Transfer function (BST) 2× - Disturbance and fault recorder...
  • Page 8 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 RED615 LINE DIFFERENTIAL PROTECTION AND CONTROL RELAY STANDARD CONFIGURATION With in-zone power transformer support IEC 61850-9-2LE PROTECTION LOCAL HMI ALSO AVAILABLE - Binary Signal Transfer function (BST) 2×...
  • Page 9 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 1. Standard configurations Description Std. conf. Line differential protection Line differential protection with directional earth-fault protection and circuit-breaker condition monitoring Line differential protection with non-directional earth-fault protection and circuit-breaker condition monitoring...
  • Page 10 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 2. Supported functions Function IEC 61850 Protection Three-phase non-directional overcurrent protection, low stage PHLPTOC Three-phase non-directional overcurrent protection, high stage PHHPTOC Three-phase non-directional overcurrent protection, PHIPTOC instantaneous stage...
  • Page 11 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 2. Supported functions, continued Function IEC 61850 Fuse failure supervision SEQSPVC Protection communication supervision PCSITPC Runtime counter for machines and devices MDSOPT Measurement Disturbance recorder RDRE Load profile record...
  • Page 12: Protection Functions

    RED615 is the ideal relay for the protection of feeders in intermittent earth-fault protection, residual overvoltage network configurations containing closed loops. Under normal protection, phase-voltage and frequency based protection and operating conditions the feeder loop is closed.
  • Page 13 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Protection communication U12 0. 0 kV U12 0. 0 kV P 0.00 kW P 0.00 kW Q 0.00 kVAr Q 0.00 kVAr IL2 0 A IL2 0 A...
  • Page 14: Supported Abb Solutions

    5. Supported ABB solutions sampled values of analog currents and voltages and the ABB’s 615 series protection and control relays together with receiving of sampled values of voltages is supported. the Substation Automation Unit COM600 constitute a genuine...
  • Page 15 COM600. The history data can be used for accurate monitoring of process and equipment performance, using Table 3. Supported ABB solutions Product Version Substation Automation Unit COM600 4.0 SP1 or later 4.1 or later (Edition 2)
  • Page 16: Control

    GOOSE communication GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V2 EN Figure 9. ABB power system example using Relion relays, Substation Automation Unit COM600 and MicroSCADA Pro/System 800xA 6. Control purposes, when applicable, or an external input or output RED615 integrates functionality for the control of a circuit module such as RIO600 can be integrated to the relay.
  • Page 17: Measurements

    9. Fault location sequence and positive-sequence current. RED615 features an optional impedance-measuring fault location function suitable for locating short-circuits in radial Furthermore, the relay monitors the phase differential, bias and distribution systems.
  • Page 18: Recorded Data

    Compared to circuit breaker maintenance. conventional combined sequence line differential protection solutions with analog pilot wire communication, RED615 relays In addition, the relay includes a runtime counter for monitoring in combination with RPW600 communication modems offer a...
  • Page 19: Access Control

    Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 and be assigned to the remote relay’s binary outputs or internal case that severe interference in the communication link, risking logics. the correct operation of the function, is detected. An alarm...
  • Page 20: Station Communication

    Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 addition, the binary input thresholds 16…176 V DC are selected Please refer to the Input/output overview table and the terminal by adjusting the relay’s parameter settings. diagrams for more detailed information about the inputs and outputs.
  • Page 21 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 For redundant Ethernet communication, the relay offers two communication. The network redundancy is based on two optical Ethernet network interfaces. Ethernet network complementary protocols defined in the IEC 62439-3 standard: redundancy can be achieved using the high-availability PRP and HSR protocols.
  • Page 22 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 COM600 Devices not supporting HSR SCADA Ethernet switch Redundancy Redundancy Redundancy IEC 61850 HSR REF620 RET620 REM620 REF615 REF615 GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN Figure 13. High availability seamless redundancy (HSR) solution The choice between the HSR and PRP redundancy protocols solution supports the connection of up to 30 615 series relays.
  • Page 23 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Client A Client B Network A Network B Managed Ethernet switch Managed Ethernet switch with RSTP support with RSTP support GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN Figure 14. Self-healing Ethernet ring solution...
  • Page 24 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 The relay supports the following high accuracy time • Layer 2 mapping synchronization method with a time-stamping resolution of 4 µs • Peer to peer delay calculation required especially in process bus applications.
  • Page 25: Technical Data

    Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 21. Technical data Table 6. Dimensions Description Value Width Frame 177 mm Case 164 mm Height Frame 177 mm (4U) Case 160 mm Depth 201 mm (153 + 48 mm)
  • Page 26 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 9. Energizing inputs (sensors) Description Value Current sensor input Rated current voltage (in secondary 75 mV...9000 mV side) Continuous voltage withstand 125 V Input impedance at 50/60 Hz 2...3 MΩ...
  • Page 27 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 13. Double-pole power output relays with TCS function Description Value Rated voltage 250 V AC/DC Continuous contact carry Make and carry for 3.0 s 15 A Make and carry for 0.5 s 30 A Breaking capacity when the control-circuit time constant L/R<40 ms, at...
  • Page 28 Maximum length depends on the cable attenuation and quality, the amount of splices and connectors in the path. Maximum allowed attenuation caused by connectors and cable altogether Use single-mode fiber with recommended minimum length of 3 m to connect RED615 to the pilot wire modem RPW600. Table 18. IRIG-B...
  • Page 29 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 21. Electromagnetic compatibility tests Description Type test value Reference 1 MHz/100 kHz burst disturbance test IEC 61000-4-18 IEC 60255-26, class III IEEE C37.90.1-2002 • Common mode 2.5 kV •...
  • Page 30 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 21. Electromagnetic compatibility tests, continued Description Type test value Reference Power frequency immunity test Binary inputs only IEC 61000-4-16 IEC 60255-26, class A • Common mode 300 V rms •...
  • Page 31 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 24. Environmental tests Description Type test value Reference Dry heat test • 96 h at +55ºC IEC 60068-2-2 • 16 h at +70ºC Dry cold test • 96 h at -25ºC IEC 60068-2-1 •...
  • Page 32 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Protection functions Table 28. Three-phase non-directional overcurrent protection (PHxPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz PHLPTOC ±1.5% of the set value or ±0.002 × I PHHPTOC ±1.5% of set value or ±0.002 ×...
  • Page 33 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 29. Three-phase non-directional overcurrent protection (PHxPTOC) main settings Parameter Function Value (Range) Step Start Value PHLPTOC 0.05...5.00 × I 0.01 PHHPTOC 0.10...40.00 × I 0.01 PHIPTOC 1.00...40.00 × I 0.01...
  • Page 34 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 31. Three-phase directional overcurrent protection (DPHxPDOC) main settings Parameter Function Value (Range) Step Start value DPHLPDOC 0.05...5.00 × In 0.01 DPHHPDOC 0.10...40.00 × In 0.01 Time multiplier DPHxPDOC 0.05...15.00...
  • Page 35 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 33. Non-directional earth-fault protection (EFxPTOC) main settings Parameter Function Value (Range) Step Start value EFLPTOC 0.010...5.000 × I 0.005 EFHPTOC 0.10...40.00 × I 0.01 EFIPTOC 1.00...40.00 × I 0.01...
  • Page 36 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 34. Directional earth-fault protection (DEFxPDEF) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz DEFLPDEF Current: ±1.5% of the set value or ±0.002 × I Voltage ±1.5% of the set value or ±0.002 ×...
  • Page 37 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 35. Directional earth-fault protection (DEFxPDEF) main settings Parameter Function Value (Range) Step Start Value DEFLPDEF 0.010...5.000 × I 0.005 DEFHPDEF 0.10...40.00 × I 0.01 Directional mode DEFLPDEF and DEFHPDEF...
  • Page 38 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 37. Admittance-based earth-fault protection (EFPADM) main settings Parameter Function Value (Range) Step Voltage start value EFPADM 0.01...2.00 × U 0.01 Directional mode EFPADM 1 = Non-directional 2 = Forward...
  • Page 39 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 39. Wattmetric-based earth-fault protection (WPWDE) main settings Parameter Function Value (Range) Step Directional mode WPWDE 2 = Forward 3 = Reverse Current start value WPWDE 0.010...5.000 × I 0.001...
  • Page 40 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 42. Harmonics-based earth-fault protection (HAEFPTOC) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz ±5% of the set value or ±0.004 × I...
  • Page 41 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 45. Negative-sequence overcurrent protection (NSPTOC) main settings Parameter Function Value (Range) Step Start value NSPTOC 0.01...5.00 × I 0.01 Time multiplier NSPTOC 0.05...15.00 0.01 Operate delay time NSPTOC 40...200000 ms...
  • Page 42 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 49. Residual overvoltage protection (ROVPTOV) main settings Parameter Function Value (Range) Step Start value ROVPTOV 0.010...1.000 × U 0.001 Operate delay time ROVPTOV 40...300000 ms Table 50. Three-phase undervoltage protection (PHPTUV)
  • Page 43 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 52. Three-phase overvoltage protection (PHPTOV) Characteristic Value Operation accuracy Depending on the frequency of the measured voltage: f ±2 Hz ±1.5% of the set value or ±0.002 × U...
  • Page 44 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 55. Positive-sequence undervoltage protection (PSPTUV) main settings Parameter Function Value (Range) Step Start value PSPTUV 0.010...1.200 × U 0.001 Operate delay time PSPTUV 40...120000 ms Voltage block value PSPTUV 0.01...1.0 ×...
  • Page 45 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 59. Frequency protection (FRPFRQ) main settings Parameter Function Value (Range) Step Operation mode FRPFRQ 1 = Freq< 2 = Freq> 3 = df/dt 4 = Freq< + df/dt 5 = Freq>...
  • Page 46 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 62. Three-phase thermal overload protection, two time constants (T2PTTR) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz Current measurement: ±1.5% of the set value or ±0.002 x I (at currents in the range of 0.01...4.00 x I...
  • Page 47 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 66. Circuit breaker failure protection (CCBRBRF) main settings Parameter Function Value (Range) Step Current value (Operating phase CCBRBRF 0.05...1.00 × I 0.05 current) Current value Res (Operating CCBRBRF 0.05...1.00 ×...
  • Page 48 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 72. Multipurpose protection (MAPGAPC) main settings Parameter Function Value (Range) Step Start value MAPGAPC -10000.0...10000.0 Operate delay time MAPGAPC 0...200000 ms Operation mode MAPGAPC Over Under Table 73. Fault locator (SCEFRFLO)
  • Page 49 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 75. Line differential protection with in-zone power transformer (LNPLDF) Characteristics Value Depending on the frequency of the measured current: f ±2 Hz Operation accuracy Low stage ±2.5% of the set value High stage ±2.5% of the set value...
  • Page 50 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 78. Operation characteristics Parameter Value (Range) Operating curve type 1 = ANSI Ext. inv. 2 = ANSI Very. inv. 3 = ANSI Norm. inv. 4 = ANSI Mod inv.
  • Page 51 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Power quality functions Table 79. Voltage variation (PHQVVR) Characteristic Value Operation accuracy ±1.5% of the set value or ±0.2% of reference voltage Reset ratio Typically 0.96 (Swell), 1.04 (Dip, Interruption) Table 80.
  • Page 52 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Control functions Table 81. Autoreclosing (DARREC) Characteristic Value Operate time accuracy ±1.0% of the set value or ±20 ms Table 82. Synchronism and energizing check (SECRSYN) Characteristic Value...
  • Page 53 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Condition monitoring and supervision functions Table 84. Circuit-breaker condition monitoring (SSCBR) Characteristic Value Current measuring accuracy ±1.5% or ±0.002 x I (at currents in the range of 0.1…10 x I ±5.0%...
  • Page 54 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Measurement functions Table 89. Three-phase current measurement (CMMXU) Characteristic Value Operation accuracy Depending on the frequency of the measured current: f ±2 Hz ±0.5% or ±0.002 × I (at currents in the range of 0.01...4.00 ×...
  • Page 55 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 94. Sequence voltage measurement (VSMSQI) Characteristic Value Operation accuracy Depending on the frequency of the voltage measured: f ±2 Hz At voltages in range 0.01…1.15 × U ±1.0% or ±0.002 ×...
  • Page 56 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Other functions Table 97. Pulse timer function block (PTGAPC) Characteristic Value Operate time accuracy ±1.0% of the set value or ±20 ms Table 98. Time delay off (8 pcs) (TOFPAGC)
  • Page 57: Local Hmi

    Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 22. Local HMI default single line diagram. The SLD view can also be accessed The relay is available with two optional displays, a large one and using the Web browser-based user interface. The default SLD a small one.
  • Page 58: Mounting Methods

    Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 23. Mounting methods Mounting methods: By means of appropriate mounting accessories the standard • Flush mounting relay case for the 615 series relay can be flush mounted, semi- •...
  • Page 59: Accessories And Ordering Data

    1MRS120547-3 3.0 meter LC-LC single-mode fiber optic patch cable for connecting one Pilot Wire modem to the RED615 relay Please note that two patch cables are required for connecting the Pilot Wire communication package (RPW600AMF). Table 103. Mounting accessories...
  • Page 60: Cyber Security

    Configuration and setting tools Version PCM600 2.6 (Rollup 20150626) or later Web browser-based user interface IE 8.0, IE 9.0, IE 10.0 or IE 11.0 RED615 Connectivity Package 5.1 or later Table 105. Supported functions Function Web HMI PCM600 Relay parameter setting ●...
  • Page 61: Terminal Diagrams

    Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 29. Terminal diagrams GUID-FBFA9940-E37D-4C32-A083-0367AAEDE267 V2 EN Figure 20. Terminal diagram for configuration A and C...
  • Page 62 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 GUID-A05D9233-4377-48D7-9F00-4218F0E7D4DC V2 EN Figure 21. Terminal diagram for configuration B...
  • Page 63 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 RED615 X100 X120 BI 1 BI 2 BI 3 BI 4 1/5A 1/5A 1/5A 1/5A X130 BI 1 BI 2 TCS1 BI 3 BI 4 TCS2 60 -...
  • Page 64 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 RED615 X130 X100 0,2/1A X131 X132 X133 TCS1 X110 BI 1 TCS2 BI 2 X110 BI 3 BI 4 BI 5 BI 6 BI 7 BI 8 1) 3)
  • Page 65: Certificates

    You will find the latest relevant information on the RED615 protection and control relay on the product page. Scroll down the page to find and download the related documentation.
  • Page 66: Functions, Codes And Symbols

    Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 32. Functions, codes and symbols Table 106. Functions included in the relay Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, low PHLPTOC1 3I> (1) 51P-1 (1)
  • Page 67 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 106. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI Three-phase overvoltage protection PHPTOV1 3U> (1) 59 (1) PHPTOV2 3U> (2) 59 (2) PHPTOV3 3U>...
  • Page 68 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 106. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI High-impedance fault detection PHIZ1 HIF (1) HIZ (1) Power quality Current total demand distortion...
  • Page 69 Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 Table 106. Functions included in the relay, continued Function IEC 61850 IEC 60617 IEC-ANSI RTD/mA measurement XRGGIO130 X130 (RTD) (1) X130 (RTD) (1) Frequency measurement FMMXU1 f (1)
  • Page 70: Document Revision History

    Line Differential Protection and Control 1MRS756500 K RED615 Product version: 5.0 FP1 33. Document revision history Document revision/date Product version History A/2008-10-03 First release B/2009-07-03 Content updated to correspond to the product version C/2010-06-11 Content updated to correspond to the product version...
  • Page 72 Medium Voltage Products, Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/mediumvoltage www.abb.com/substationautomation ABB India Limited, Distribution Automation Maneja Works Vadodara-390013, India Phone +91 265 6724402 +91 265 6724423 www.abb.com/mediumvoltage www.abb.com/substationautomation...

Table of Contents