reaches its closed position. The travel times are calculated based on the state
changes of the auxiliary contacts and the adding correction factor to consider the
time difference of the main contact's and the auxiliary contact's position change.
Operation counter
Routine maintenance of the breaker, such as lubricating breaker mechanism, is
generally based on a number of operations. A suitable threshold setting to raise an
alarm when the number of operation cycle exceeds the set limit helps preventive
maintenance. This can also be used to indicate the requirement for oil sampling for
dielectric testing in case of an oil circuit breaker.
The change of state can be detected from the binary input of the auxiliary contact.
There is a possibility to set an initial value for the counter which can be used to
initialize this functionality after a period of operation or in case of refurbished
primary equipment.
y
Accumulation of I
t
y
Accumulation of I
t calculates the accumulated energy ΣI
known as the current exponent. The factor y depends on the type of the circuit
breaker. For oil circuit breakers, the factor y is normally 2. In case of a high-
voltage system, the factor y can be 1.4...1.5.
Remaining life of the breaker
Every time the breaker operates, the life of the circuit breaker reduces due to
wearing. The wearing in the breaker depends on the tripping current, and the
remaining life of the breaker is estimated from the circuit breaker trip curve
provided by the manufacturer.
Example for estimating the remaining life of a circuit breaker
Condition monitoring functions
y
t, where the factor y is