Str 3 delay shot 1
Str 3 delay shot 2
Str 3 delay shot 3
Str 3 delay shot 4
Time delay settings for the DEL_INIT_4 signal are as follows:
Str 4 delay shot 1
Str 4 delay shot 2
Str 4 delay shot 3
Str 4 delay shot 4
Normally, only two or three reclose attempts are made. The third and fourth times
are used to provide the so called fast final trip to lockout.
PHLPTOC
OPERATE
I_A
I_B
START
I_C
BLOCK
ENA_MULT
CB_POSITION
CB_ READY
A070866 V3 EN
Figure 376:
Autoreclose configuration example
Delayed DEL_INIT_2...4 signals are used only when the auto-reclose shot is
initiated with the start signal of a protection stage. After a start delay, the AR
function opens the circuit breaker and an auto-reclose shot is initiated. When the
shot is initiated with the trip signal of the protection, the protection function trips
the circuit breaker and simultaneously initiates the auto-reclose shot.
If the circuit breaker is manually closed against the fault, that is, if SOTF is used,
the fourth time delay can automatically be taken into use. This is controlled with
the internal logic of the AR function and the Fourth delay in SOTF parameter.
A typical auto-reclose situation is where one auto-reclose shot has been performed
after the fault was detected. There are two types of such cases: operation initiated
with protection start signal and operation initiated with protection trip signal. In
both cases, the auto-reclose sequence is successful: the reclaim time elapses and no
new sequence is started.
DARREC
INIT_1
OPEN _CB
INIT_2
CLOSE _CB
INIT_3
CMD_W AIT
INPRO
INIT_4
LOCKED
INIT_5
PROT _CRD
INIT_6
UNSUC_RECL
DEL_ INIT_2
DEL_ INIT_3
AR_ON
DEL_ INIT_4
READY
BLK _RECL _T
BLK _RCLM_T
BLK _THERM
CB_POS
CB_READY
INC_ SHOTP
INHIBIT_ RECL
RECL_ON
SYNC
Section 9
Control functions
OR
CB_TRIP
CB_CLOSE
697