ABB RED615 Technical Manual page 227

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
Parameter
Values (Range)
Operating curve type
Type of reset curve
Directional mode
Characteristic angle
Max forward angle
Max reverse angle
Min forward angle
Min reverse angle
Pol quantity
Table 224:
DPH3LPDOC Non group settings
Parameter
Values (Range)
Operation
Num of start phases
Minimum operate time
Reset delay time
Measurement mode
Curve parameter A
Curve parameter B
Table continues on next page
615 series
Technical Manual
Unit
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
1=Immediate
2=Def time reset
3=Inverse reset
1=Non-directional
2=Forward
3=Reverse
-179...180
deg
0...90
deg
0...90
deg
0...90
deg
0...90
deg
-2=Pos. seq. volt.
1=Self pol
4=Neg. seq. volt.
5=Cross pol
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
0.0086...120.0000
0.0000...0.7120
Step
Default
15=IEC Def. Time
1=Immediate
2=Forward
1
60
1
80
1
80
1
80
1
80
5=Cross pol
Step
Default
1=on
1=1 out of 3
10
20
10
20
2=DFT
28.2000
0.1217
Section 4
Protection functions
Description
Selection of time delay curve type
Selection of reset curve type
Directional mode
Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Reference quantity used to determine
fault direction
Description
Operation Off / On
Number of phases required for operate
activation
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
221