ABB RED615 Technical Manual page 288

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Section 4
Protection functions
282
GUID-67BE307E-576A-44A9-B615-2A3B184A410D V2 EN
Figure 137:
Definition of the relay characteristic angle, RCA=–90 degrees in an
isolated network
Directional earth-fault protection in an isolated neutral network
In isolated networks, there is no intentional connection between the system neutral
point and earth. The only connection is through the phase-to-earth capacitances
(C
) of phases and leakage resistances (R
0
mainly capacitive and has a phase shift of –90 degrees compared to the polarizing
voltage. Consequently, the relay characteristic angle (RCA) should be set to -90
degrees and the operation criteria to "IoSin" or "Phase angle". The width of the
operating sector in the phase angle criteria can be selected with the settings Min
forward angle, Max forward angle, Min reverse angle or Max reverse angle.
Figure 138
illustrates a simplified equivalent circuit for an unearthed network with
an earth fault in phase C.
For definitions of different directional earth-fault characteristics,
see
Directional earth-fault principles
). This means that the residual current is
0
.
1YHT530004D05 D
615 series
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents