Section 3
Basic functions
64
A070704 V3 EN
Figure 9:
Programmable LEDs on the right side of the display
All the programmable LEDs in the HMI of the IED have two colors, green and red.
For each LED, the different colors are individually controllable.
Each LED has two control inputs, ALARM and OK. The color setting is common for
all the LEDs. It is controlled with the Alarm color setting, the default value being
"Red". The OK input corresponds to the color that is available, with the default
value being "Green".
Changing the Alarm color setting to "Green" changes the color behavior of the OK
inputs to red.
The ALARM input has a higher priority than the OK input.
Each LED is seen in the Application Configuration tool as an individual function
block. Each LED has user-editable description text for event description. The state
("None", "OK", "Alarm") of each LED can also be read under a common
monitored data view for programmable LEDs.
1YHT530004D05 D
REF615
Overcurrent
Dir. earth-fault
Voltage protection
Phase unbalance
Thermal overload
Breaker failure
Disturb. rec. Triggered
CB condition monitoring
Supervision
Arc detected
Autoreclose shot in progr.
615 series
Technical Manual