ABB RED615 Technical Manual page 399

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
615 series
Technical Manual
Charact.
I_D
(from Differential calculation)
I
I_B
(from Differential calculation)
BLOCK
I
bias
BLOCK_OPR_LS
Slope section 2
End section 2
Low operate value
Fault in protected area
(from Differential calculation)
AND
BLKD2HPHAR_A
(from Second harmonic blocking)
AND
BLKD2HPHAR_A
(from Second harmonic blocking)
AND
BLKD2HPHAR_C
(from Second harmonic blocking)
AND
BLKD5HPHAR_A
(from Fifth harmonic blocking)
AND
BLKD5HPHAR_B
(from Fifth harmonic blocking)
AND
BLKD5HPHAR_C
(from Fifth harmonic blocking)
AND
BLKDWAV_A
(from Waveform blocking)
AND
BLKDWAV_B
(from Waveform blocking)
AND
BLKDWAV_C
(from Waveform blocking))
GUID-0E927DF9-5641-4CAE-B808-0B75EA09EA95 V2 EN
Figure 209:
Operation logic of the biased low stage
The high currents passing through a protected object can be caused by the short
circuits outside the protected area, the large currents fed by the transformer in
motor startup or the transformer inrush situations. Therefore, the operation of the
differential protection is biased in respect to the load current. In biased differential
protection, the higher the differential current required for the protection to operate,
the higher the load current.
The operating characteristic of the biased low stage is determined by Low operate
value, Slope section 2 and the setting of the second turning point of the operating
characteristic curve, End section 2 (the first turning point and the slope of the last
part of the characteristic are fixed). The settings are the same for all the phases.
When the differential current exceeds the operating value determined by the
operating characteristic, the differential function awakes. If the differential current
stays above the operating value continuously for a suitable period, which is 1.1
times the fundamental cycle, the OPR_LS output is activated. The OPERATE
output is always activated when the OPR_LS output is activated.
The stage can be blocked internally by the second or fifth harmonic restraint, or by
special algorithms detecting inrush and current transformer saturation at external
Protection functions
OR
AND
OR
AND
OR
AND
OR
AND
AND
AND
AND
AND
AND
AND
AND
AND
Section 4
OPERATE
OPR_LS
BLKD2H
OR
BLKD5H
OR
BLKDWAV
OR
393