ABB RED615 Technical Manual page 190

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Section 4
Protection functions
184
GUID-CD0B7D5A-1F1A-47E6-AF2A-F6F898645640 V2 EN
Figure 88:
Configurable operating sectors
Table 194:
Momentary per phase direction value for monitored data view
Criterion for per phase direction information
The ANGLE_X is not in any of the defined
sectors, or the direction cannot be defined due
too low amplitude
The ANGLE_X is in the forward sector
The ANGLE_X is in the reverse sector
(The ANGLE_X is in both forward and reverse
sectors, that is, when the sectors are overlapping)
Table 195:
Momentary phase combined direction value for monitored data view
Criterion for phase combined direction information The value for DIRECTION
The direction information (DIR_X) for all phases
is unknown
The direction information (DIR_X) for at least one
phase is forward, none being in reverse
The direction information (DIR_X) for at least one
phase is reverse, none being in forward
The direction information (DIR_X) for some
phase is forward and for some phase is reverse
The value for DIR_A/_B/_C
0 = unknown
1 = forward
2 = backward
3 = both
0 = unknown
1 = forward
2 = backward
3 = both
1YHT530004D05 D
615 series
Technical Manual