1YHT530004D05 D
Parameter
Values (Range)
Max reverse angle
Min forward angle
Min reverse angle
Voltage start value
Enable voltage limit
Table 301:
DEFLPDEF Non group settings
Parameter
Values (Range)
Operation
Reset delay time
Minimum operate time
Allow Non Dir
Measurement mode
Min operate current
Min operate voltage
Correction angle
Pol reversal
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Io signal Sel
Pol signal Sel
615 series
Technical Manual
Unit
0...180
deg
0...180
deg
0...180
deg
0.010...1.000
xUn
0=False
1=True
Unit
1=on
5=off
0...60000
ms
60...60000
ms
0=False
1=True
1=RMS
2=DFT
3=Peak-to-Peak
0.005...1.000
xIn
0.01...1.00
xUn
0.0...10.0
deg
0=False
1=True
0.0086...120.0000
0.0000...0.7120
0.02...2.00
0.46...30.00
0.0...1.0
1=Measured Io
2=Calculated Io
1=Measured Uo
2=Calculated Uo
3=Neg. seq. volt.
Step
Default
1
80
1
80
1
80
0.001
0.010
1=True
Step
Default
1=on
1
20
1
60
0=False
2=DFT
0.001
0.005
0.01
0.01
0.1
0.0
0=False
28.2000
0.1217
2.00
29.10
1.0
1=Measured Io
1=Measured Uo
Section 4
Protection functions
Description
Maximum phase angle in reverse
direction
Minimum phase angle in forward direction
Minimum phase angle in reverse direction
Voltage start value
Enable voltage limit
Description
Operation Off / On
Reset delay time
Minimum operate time for IDMT curves
Allows prot activation as non-dir when dir
info is invalid
Selects used measurement mode
Minimum operating current
Minimum operating voltage
Angle correction
Rotate polarizing quantity
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer
programmable curve
Parameter D for customer
programmable curve
Parameter E for customer programmable
curve
Selection for used Io signal
Selection for used polarization signal
299