ABB RED615 Technical Manual page 202

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

Section 4
Protection functions
Table 204:
DPHLPDOC Non group settings
Parameter
Operation
Num of start phases
Minimum operate time
Reset delay time
Measurement mode
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Allow Non Dir
Min operate current
Min operate voltage
Table 205:
DPHHPDOC Group settings
Parameter
Start value
Start value Mult
Directional mode
Time multiplier
Operating curve type
Type of reset curve
Operate delay time
Characteristic angle
Table continues on next page
196
Values (Range)
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
0.0086...120.0000
0.0000...0.7120
0.02...2.00
0.46...30.00
0.0...1.0
0=False
1=True
0.01...1.00
xIn
0.01...1.00
xUn
Values (Range)
Unit
0.10...40.00
xIn
0.8...10.0
1=Non-directional
2=Forward
3=Reverse
0.05...15.00
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
1=Immediate
2=Def time reset
3=Inverse reset
40...200000
ms
-179...180
deg
Step
Default
1=on
1=1 out of 3
1
20
1
20
2=DFT
28.2000
0.1217
2.00
29.10
1.0
0=False
0.01
0.01
0.01
0.01
Step
Default
0.01
0.10
0.1
1.0
2=Forward
0.01
1.00
15=IEC Def. Time
1=Immediate
10
40
1
60
1YHT530004D05 D
Description
Operation Off / On
Number of phases required for operate
activation
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer
programmable curve
Parameter D for customer
programmable curve
Parameter E for customer programmable
curve
Allows prot activation as non-dir when dir
info is invalid
Minimum operating current
Minimum operating voltage
Description
Start value
Multiplier for scaling the start value
Directional mode
Time multiplier in IEC/ANSI IDMT curves
Selection of time delay curve type
Selection of reset curve type
Operate delay time
Characteristic angle
Technical Manual
615 series