I
rated load of the power transformer
nT
S
rated power of the power transformer
n
U
rated phase-to-phase voltage
n
Next, the settings for the CT ratio correction can be calculated with the formula:
CT ratio correction
=
GUID-F950DE9C-6AFB-4DF9-B299-6631693C55C0 V1 EN
I
nominal primary current of the CT
n
After the CT ratio correction, the measured currents and corresponding setting
values of LNPLDF are expressed in multiples of the rated power transformer
current Ir (×Ir) or percentage value of Ir (%Ir).
An example shows how the CT ratio correction settings are calculated; when the
rated power of the transformer is 5 MVA, the ratio of CTs on the 20 kV side is
200/1 and that on the 10.5 kV side is 300/1.
GUID-74289FF5-E90D-4633-9FEE-04DB8E86A3AE V1 EN
Figure 184:
Example of CT ratio correction setting calculation with in-zone
transformer
The rated load of the transformer is:
HV side (A): I
= 5 MVA / (1.732 × 20 kV) = 144.3 A
nT_A
I
n
I
nT
Section 4
Protection functions
(Equation 31)
(Equation 32)
351