Figure 191:
Operation logic of the direct intertrip function
The start and operate signals are provided separately for the low and high stages,
and in the local and remote.
Blocking functionality
There are two independent inputs that can be used for blocking the function:
BLOCK and BLOCK_LS. The difference between these inputs is that BLOCK_LS
(when TRUE) blocks only the stabilized low stage leaving the instantaneous high
stage operative. BLOCK (when TRUE) blocks both stages and also the
PROT_ACTIVE output is updated according to the BLOCK input status, as
described in the Fail safe function chapter.
The BLOCK and BLOCK_LS input statuses affect only the behavior of the local
protection instance. When a line differential protection stage (stabilized low or
instantaneous high) is blocked, also the received remote signals related to the
Protection functions
OR
OR
OR
SEND
OR
SEND
OR
SEND
OR
OR
OR
Section 4
OPERATE
START
OPR_HS_LOC
OPR_LS_LOC
STR_LS_LOC
OPR_HS_REM
OPR_LS_REM
STR_LS_REM
365