Once activated, the timer activates the START output. Depending on the value of
the Operating curve type setting, the time characteristics are according to DT or
IDMT. When the operation timer has reached the value of Operate delay time in
the DT mode or the maximum value defined by the inverse time curve, the
OPERATE output is activated.
When the user-programmable IDMT curve is selected, the operation time
characteristics are defined by the parameters Curve parameter A, Curve parameter
B, Curve parameter C, Curve parameter D and Curve parameter E.
If a drop-off situation happens, that is, a fault suddenly disappears before the
operate delay is exceeded, the timer reset state is activated. The functionality of the
timer in the reset state depends on the combination of the Operating curve type,
Type of reset curve and Reset delay time settings. When the DT characteristic is
selected, the reset timer runs until the set Reset delay time value is exceeded. When
the IDMT curves are selected, the Type of reset curve setting can be set to
"Immediate", "Def time reset" or "Inverse reset". The reset curve type "Immediate"
causes an immediate reset. With the reset curve type "Def time reset", the reset
time depends on the Reset delay time setting. With the reset curve type "Inverse
reset", the reset time depends on the current during the drop-off situation. The
START output is deactivated when the reset timer has elapsed.
The "Inverse reset" selection is only supported with ANSI or user
programmable types of the IDMT operating curves. If another
operating curve type is selected, an immediate reset occurs during
the drop-off situation.
The setting Time multiplier is used for scaling the IDMT operate and reset times.
The setting parameter Minimum operate time defines the minimum desired operate
time for IDMT. The setting is applicable only when the IDMT curves are used.
The Minimum operate time setting should be used with great care
because the operation time is according to the IDMT curve, but
always at least the value of the Minimum operate time setting. For
more information, see the
section in this manual.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operating time. The value is
available in the monitored data view.
Blocking logic
There are three operation modes in the blocking functionality. The operation modes
are controlled by the BLOCK input and the global setting "Configuration/System/
Blocking mode" which selects the blocking mode. The BLOCK input can be
IDMT curves for overcurrent protection