A070870 V1 EN
Figure 387:
Logic diagram of auto-initiation sequence detection
Automatic initiation can be selected with the Auto initiation Cnd setting to be the
following:
Not allowed: no automatic initiation is allowed
When the synchronization fails, the automatic initiation is carried out when the
auto wait time elapses and the reclosing is prevented due to a failure during the
synchronism check
When the circuit breaker does not close, the automatic initiation is carried out
if the circuit breaker does not close within the wait close time after issuing the
reclose command
Both: the automatic initiation is allowed when synchronization fails or the
circuit breaker does not close.
Section 9
Control functions
713