1YHT530004D05 D
615 series
Technical Manual
Table 699:
Ethernet interfaces
Ethernet interface
Protocol
Front
TCP/IP
protocol
Rear
TCP/IP
protocol
Table 700:
Serial rear interface
Type
Serial port (X5)
Serial port (X16)
Serial port (X12)
1) Depending on the optional communication module
Table 701:
Fibre-optic communication link
Connector
Fibre type
LC
MM 62.5/125 or
50/125 μm glass
fibre core
ST
MM 62.5/125 or
50/125 μm glass
fibre core
1) Maximum allowed attenuation caused by connectors and cable together
Table 702:
Fibre-optic protection communication link available in RED615
Connector
Fibre type
LC
MM 62.5/125 or
50/125 μm
LC
SM 9/125 μm
1) Maximum allowed attenuation caused by connectors and cable altogether
2) Use single-mode fibre with recommended minimum length of 3 m to connect RED615 to the pilot
wire modem RPW600.
Table 703:
IRIG-B
Description
IRIG time code format
Isolation
Modulation
Table continues on next page
Cable
Standard Ethernet CAT 5 cable with RJ-45
connector
Shielded twisted pair CAT 5e cable with
RJ-45 connector or fibre-optic cable with LC
connector
Counter connector
10-pin counter connector Weidmüller BL
3.5/10/180F AU OR BEDR
or
9-pin counter connector Weidmüller BL
3.5/9/180F AU OR BEDR
9-pin D-sub connector DE-9
Optical ST-connector
Wave length
Max. distance
1300 nm
2 km
820-900 nm
1 km
Wave length
Max. distance
1300 nm
2 km
2)
1300 nm
20 km
Value
B004, B005
500V 1 min.
Unmodulated
Section 14
Technical data
Data transfer rate
10 MBits/s
100 MBits/s
1)
Permitted path attenuation
<8 dB
<11 dB
Permitted path attenuation
< 8 dB
< 8 dB
1)
1)
1)