615 series
Technical Manual
DEL_INIT_2
DEL_INIT_3
DEL_INIT_4
DEL_INIT_2 and INIT_2 are connected together with an OR-gate, as are inputs
3 and 4. Inputs 1, 5 and 6 do not have any delayed input. From the auto-reclosing
point of view, it does not matter whether INIT_x or DEL_INIT_x line is used
for shot initiation or blocking.
The auto-reclose function can also open the circuit breaker from any of the
initiation lines. It is selected with the Tripping line setting. As a default, all
initiation lines activate the OPEN_CB output.
A070276 V1 EN
Figure 394:
Simplified logic diagram of initiation lines
Each delayed initiation line has four different time settings:
Table 620:
Settings for delayed initiation lines
Setting name
Str x delay shot 1
Str x delay shot 2
Str x delay shot 3
Str x delay shot 4
Control functions
Description and purpose
Time delay for the DEL_INIT_x line, where x is
the number of the line 2, 3 or 4. Used for shot 1.
Time delay for the DEL_INIT_x line, used for
shot 2.
Time delay for the DEL_INIT_x line, used for
shot 3.
Time delay for the DEL_INIT_x line, used for
shots 4 and 5. Optionally, can also be used with
SOTF.