ABB RED615 Technical Manual page 367

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
615 series
Technical Manual
Vector group of the
Winding 1 type
transformer
Zd8
ZNd8
Zd10
ZNd10
Zz0
ZNz0
ZNzn0
Zzn0
Zz2
ZNz2
ZNzn2
Zzn2
Zz4
ZNz4
ZNzn4
Zzn4
Zz6
ZNz6
ZNzn6
Zzn6
Zz8
ZNz8
ZNzn8
Zzn8
Zz10
ZNz10
ZNzn10
Zzn10
Zero-sequence component elimination
If Clock number is "Clk Num 2", "Clk Num 4", "Clk Num 8" or "Clk Num 10",
the vector group matching is always done on both, winding 1 and winding 2. The
combination results in the correct compensation. In this case the zero-sequence
component is always removed from both sides automatically. The Zro A
elimination parameter cannot change this.
If Clock number is "Clk Num 1", "Clk Num 5", "Clk Num 7" or "Clk Num 11",
the vector group matching is done on one side only. A possible zero-sequence
component of the phase currents at earth faults occurring outside the protection
area is automatically eliminated in the numerically implemented delta connection
Winding 2 type
Z
d
ZN
d
Z
d
ZN
d
Z
z
ZN
z
ZN
zn
Z
zn
Z
z
ZN
z
ZN
zn
Z
zn
Z
z
ZN
z
ZN
zn
Z
zn
Z
z
ZN
z
ZN
zn
Z
zn
Z
z
ZN
z
ZN
zn
Z
zn
Z
z
ZN
z
ZN
zn
Z
zn
Section 4
Protection functions
Phase shift
Zero sequence
current elimination
8
Not needed
8
(Automatic)
10
Not needed
10
(Automatic)
0
Not needed
0
HV side
0
HV & LV side
0
LV side
2
Not needed
2
(Automatic)
2
(Automatic)
2
(Automatic)
4
Not needed
4
(Automatic)
4
(Automatic)
4
(Automatic)
6
Not needed
6
HV side
6
HV & LV side
6
LV side
8
Not needed
8
(Automatic)
8
(Automatic)
8
(Automatic)
10
Not needed
10
(Automatic)
10
(Automatic)
10
(Automatic)