1YHT530004D05 D
615 series
Technical Manual
differential current. The elimination of the zero-sequence component can be
selected for that winding by setting the Zro A elimination parameter.
Table 339:
TR2PTDF settings corresponding to the power transformer vector groups and zero-
sequence elimination
Vector group of the
Winding 1 type
transformer
Yy0
Y
YNy0
YN
YNyn0
YN
Yyn0
Y
Yy2
Y
YNy2
YN
YNyn2
YN
Yyn2
Y
Yy4
Y
YNy4
YN
YNyn4
YN
Yyn4
Y
Yy6
Y
YNy6
YN
YNyn6
YN
Yyn6
Y
Yy8
Y
YNy8
YN
YNyn8
YN
Yyn8
Y
Yy10
Y
YNy10
YN
YNyn10
YN
Yyn10
Y
Yd1
Y
YNd1
YN
Yd5
Y
YNd5
YN
Yd7
Y
YNd7
YN
Yd11
Y
YNd11
YN
Dd0
D
Dd2
D
Dd4
D
Table continues on next page
Protection functions
Winding 2 type
Clock number
y
Clk Num 0
y
Clk Num 0
yn
Clk Num 0
yn
Clk Num 0
y
Clk Num 2
y
Clk Num 2
yn
Clk Num 2
yn
Clk Num 2
y
Clk Num 4
y
Clk Num 4
yn
Clk Num 4
yn
Clk Num 4
y
Clk Num 6
y
Clk Num 6
yn
Clk Num 6
yn
Clk Num 6
y
Clk Num 8
y
Clk Num 8
yn
Clk Num 8
yn
Clk Num 8
y
Clk Num 10
y
Clk Num 10
yn
Clk Num 10
yn
Clk Num 10
d
Clk Num 1
d
Clk Num 1
d
Clk Num 5
d
Clk Num 5
d
Clk Num 7
d
Clk Num 7
d
Clk Num 11
d
Clk Num 11
d
Clk Num 0
d
Clk Num 2
d
Clk Num 4
Section 4
Zro A Elimination
Not needed
HV side
HV & LV side
LV side
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
HV side
HV & LV side
LV side
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
Not needed
403