ABB RED615 Technical Manual page 293

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
4.2.2.8
615 series
Technical Manual
Table 293:
Reset time characteristics supported by different stages
Reset curve type
(1) Immediate
(2) Def time reset
(3) Inverse reset
Directional earth-fault characteristics
Phase angle characteristic
The operation criterion phase angle is selected with the Operation mode setting
using the value "Phase angle".
When the phase angle criterion is used, the function indicates with the
DIRECTION output whether the operating quantity is within the forward or
reverse operation sector or within the non-directional sector.
The forward and reverse sectors are defined separately. The forward operation area
is limited with the Min forward angle and Max forward angle settings. The reverse
operation area is limited with the Min reverse angle and Max reverse angle settings.
The sector limits are always given as positive degree values.
In the forward operation area, the Max forward angle setting gives the clockwise
sector and the Min forward angle setting correspondingly the counterclockwise
sector, measured from the Characteristic angle setting.
In the reverse operation area, the Max reverse angle setting gives the clockwise
sector and the Min reverse angle setting correspondingly the counterclockwise
sector, measured from the complement of the Characteristic angle setting (180
degrees phase shift) .
The relay characteristic angle (RCA) is set to positive if the operating current lags
the polarizing quantity. It is set to negative if it leads the polarizing quantity.
Supported by
DEFLPDEF
DEFHPDEF
x
x
x
Section 4
Protection functions
Note
x
Available for all
operate time curves
x
Available for all
operate time curves
x
Available only for ANSI
and user
programmable curves
287

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents