ABB RED615 Technical Manual page 741

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
615 series
Technical Manual
[ ]
Line drop V Ris U
=
%
r
[ ]
Line dro
p p V React U
=
%
x
GUID-B79F4E6B-B70E-4D85-BD8C-7877BD52A334 V1 EN
I
Nominal primary current of the CT
CT_n1
U
Nominal primary voltage of the VT (phase-to-phase voltage)
VT_n1
R
Resistance of the line, Ω/phase
X
Reactance of the line, Ω/phase
The general LDC equation can be calculated.
(
[ ]
I
U
% cos
injected
r
U
=
×
z
I
n
GUID-B004A188-862D-4015-868D-8654F8F5D214 V1 EN
I
Average of the currents I_A, I_B and I_C
injected
U
Setting
Line drop V Ris
r
Line drop V React
U
Setting
x
φ
Phase angle between U_A and I_A (ANGL_UA_IA in monitored data)
By default, the line drop compensation (LDC) is not active. LDC is activated by
setting LDC enable to "True". To keep the LDC term within acceptable limits in all
situations, OLATCC has a setting parameter LDC limit, which has a default value
of 0.10 xU
. As a result, this gives the maximum value for U
n
If more than one line is connected to the LV busbar, the equivalent impedance is
calculated and given as a parameter setting as shown in
equivalent electrical circuit for calculating LDC. For example, if there are N
number of identical lines with identical loads in the substation, the R- and X-values
needed for the settings Line drop V React and Line drop V Ris are obtained by
dividing the resistance and the reactance of one line by N. Because the voltage
drop is different in lines with different impedances and load currents, it is
necessary to make a compromise when setting the Line drop V React and Line drop
V Ris settings. Raising the voltage in the point of lowest voltage must not lead to
overvoltage elsewhere.
By default, the line drop compensation is effective only on the normal active power
flow direction. If the active power flow in the transformer turns opposite, that is,
from the regulated side towards the system in the upper level, the LDC term is
ignored, that is, set to zero. In such a case, it is assumed that the feeding units at the
regulated side of the transformers maintain proper voltage levels. This can cause a
conflict if the transformer tries to reduce the voltage at the substation. Additionally,
3
×
I
×
R
CT n
_
1
=
×
100
U
VT n
_
1
3
×
I
×
X
CT n
_
1
=
×
100
U
VT n
_
1
)
[ ]
+
U
% sin
ϕ
ϕ
x
[
xU
100
Section 9
Control functions
[
]
%U
n
[
]
%
U
n
]
n
in
Equation
z
Figure 398
for the
(Equation 90)
(Equation 91)
89.
735

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents