ABB RED615 Technical Manual page 159

615 series
Hide thumbs Also See for RED615:
Table of Contents

Advertisement

1YHT530004D05 D
Parameter
Values (Range)
Operate delay time
Operating curve type
Type of reset curve
Table 161:
PHLPTOC Non group settings
Parameter
Values (Range)
Operation
Num of start phases
Minimum operate time
Reset delay time
Measurement mode
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
615 series
Technical Manual
Unit
40...200000
ms
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
1=Immediate
2=Def time reset
3=Inverse reset
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
0.0086...120.0000
0.0000...0.7120
0.02...2.00
0.46...30.00
0.0...1.0
Step
Default
10
40
15=IEC Def. Time
1=Immediate
Step
Default
1=on
1=1 out of 3
1
20
1
20
2=DFT
28.2000
0.1217
2.00
29.10
1.0
Section 4
Protection functions
Description
Operate delay time
Selection of time delay curve type
Selection of reset curve type
Description
Operation Off / On
Number of phases required for operate
activation
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer
programmable curve
Parameter D for customer
programmable curve
Parameter E for customer programmable
curve
153